UL1015

UL1015

Product Code :   UL 1015

These cables are used for internal wiring of panels and electrical equipment. These are used as connection wire in machines laid in protective tubes and flexible pipes and also for motors and transformers.

Share Product


Standard UL - Std. 758, CSA C 22.2 No. 210
Nominal Voltage 600V
UL type AWM 105°C 600V
CSA type AWM 105°C 600V
Test Voltage (Spark Test) 6 KV
Temperature Range Flexing -5°C to +105°C. Fixed installation -20°C to +105°C
Temperature at Conductor Max. UL and CSA : +105°C
Bending Radius Flexing 10 x cable &‌Oslash;'. Fixed installation 5 x cable &‌Oslash;
Cable Construction Annealed plain or tinned stranded copper conductor.
PVC - core insulation according to UL - Standard 1581, Class 43 Tab. 50.182, heat and damp resistant.

Product Specifications

Conductor -Anealed Bare Copper ( ABC) Insulation- PVC Ampacity Net
Gauge No of Strand CSA Dia. Max.DC Resistance Thickness in mm Wire dia of Wire Weight
Srands dia. in mm mm2 mm Ohms/km`@ 20°C Nom. Min. Nom., mm Amp. kg/km
AWG 30/7/38 7 0.10 0.05 0.31 340.3 0.76 0.68 1.83 0.5 3.2
AWG 28/7/36 7 0.13 0.09 0.39 211.0 0.76 0.68 1.91 0.9 3.8
AWG 26/7/34 7 0.16 0.14 0.49 132.9 0.76 0.68 2.01 1.4 4.5
AWG 24/7/32 7 0.20 0.22 0.61 85.1 0.76 0.68 2.13 2.2 5.5
AWG 22/17/34 17 0.16 0.34 0.77 54.7 0.76 0.68 2.29 3.4 7.1
AWG 20/16/32 16 0.20 0.50 0.93 37.2 0.76 0.68 2.45 5.0 9.0
AWG 19/24/33 24 0.20 0.75 1.14 24.8 0.76 0.68 2.66 7.5 11.8
AWG 18/17/30 17 0.254 0.86 1.21 21.7 0.76 0.68 2.73 8.6 13.0
AWG 16/26/30 26 0.254 1.32 1.50 14.2 0.76 0.68 3.02 13.2 18.0
AWG 15/30/30 30 0.254 1.52 1.61 12.3 0.76 0.68 3.13 15.2 20.1
AWG 14/40/30 40 0.254 2.03 1.86 9.2 0.76 0.68 3.38 20.3 25.5
AWG 12/65/30 65 0.254 3.29 2.38 5.7 0.76 0.68 3.90 32.9 38.5
AWG 10/65/28 65 0.32 5.22 2.99 3.6 0.76 0.68 4.51 52.2 58.0